Viessmann Boiler: Raising reduced room temperature by outdoor temperature

Updated · by Aurora Star Tech Inc.

Raising reduced room temperature by outdoor temperature on a Viessmann boiler: During reduced room temperature operation the reduced setpoint can rise with outdoor temperature, following the heating curve, but never above the standard room setpoint.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Heating circuit reduced mode

How to fix raising reduced room temperature by outdoor temperature: step by step

  1. Set the outdoor temperature start limit for the raise at coding address F8.
  2. Set the outdoor temperature end limit for the raise at coding address F9.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

More other tips for boiler

Source: Vitodens 200-W B2HB service instructions, p. 90. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.