Viessmann Boiler: Raising reduced room temperature by outdoor temperature
Raising reduced room temperature by outdoor temperature on a Viessmann boiler: During reduced room temperature operation the reduced setpoint can rise with outdoor temperature, following the heating curve, but never above the standard room setpoint.
Applies to: Heating circuit reduced mode
How to fix raising reduced room temperature by outdoor temperature: step by step
- Set the outdoor temperature start limit for the raise at coding address F8.
- Set the outdoor temperature end limit for the raise at coding address F9.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
Source: Vitodens 200-W B2HB service instructions, p. 90. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.