Warming things up…Dialing in your comfort…Almost cozy…
Reliable Heating and Cooling Solutions – Quality Service, Fair Prices, Guaranteed Satisfaction!

Other: Boiler tips (part 28 of 45)

Updated · by Aurora Star Tech Inc.

Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.

Protect internal components from static discharge

Viessmann · Vitotronic 100 GC1 and Vitocontrol-S VD2/CT3/CM2 control unit

Static discharge can damage the internal electronics whenever the control is open.

  1. Discharge static from yourself before touching internal parts of an opened control.
  2. Avoid any static discharge to the internal components while the control is open.

Protect piping against freezing when the building is unattended

Viessmann · Vitodens 100-W B1HE/B1KE

The boiler is not designed to protect water pipes from freezing. If the boiler stays off in cold weather, pipes can freeze and burst.

  1. If the building will be empty in cold weather, shut off the water supply and drain the pipes.
  2. Add a potable-water antifreeze to drain traps and toilet tanks, and open faucets where appropriate.
  3. Alternatively, have someone check the building often or install a remote temperature sensor that alerts someone to freezing conditions.

Protect the burner tube during service

Viessmann · Vitodens 200-W B2HB 19 to 125

The burner tube is easily damaged and can cause improper operation.

  1. Do not lay the burner on its cylindrical tube.
  2. Do not touch the burner tube mesh.

Protect the electronics from static discharge

Viessmann · Vitotronic 300 GW6B control unit

Electronic assemblies can be damaged by static. Discharge yourself before work by touching a grounded object such as a heating or water pipe.

  1. Touch a grounded object such as a heating or water pipe before touching the PCB or assemblies.

Protect the gas ignition components from water

Viessmann · All Vitodens 100-W boilers

Gas ignition system components must be protected from spray and splashing during boiler operation and service.

  1. Check that the gas ignition components are shielded from water before running the boiler.
  2. Keep them shielded during service work.

Protect the heating system from high temperature

Viessmann · System layout 4 with high-temperature heating circuit

Install the optional high limit safety control on heating circuit E when there are no automatic mixing valves or when DHW priority is not required.

  1. If the heating circuit has no automatic mixing valve, fit the optional high limit safety control on heating circuit E.
  2. Also fit it if DHW priority is not used.

Protect the top panel during piping and venting work

Viessmann · VR1 22 to 33, 91 to 140

Do not stand on the top panel of the boiler when installing piping or venting, or when insulating overhead pipes. Tell other trades.

Provide proper combustion and ventilation air

Viessmann · Vitorond 200 VD2 boilers

Installation must provide adequate combustion and ventilation air. Keep chemicals that can form harmful combustion by-products out of the boiler room. See the Mechanical Room section for the chemical list and air requirements.

Pump connection terminals in typical layout

Viessmann · Vitotronic 100 KW10B typical layout (one direct-connected heating circuit without mixing valve)

In the typical one direct-connected heating circuit layout, the boiler/space heater pump connects to the pump connection (terminal 20, used with the listed boilers). The DHW pump connects to the DHW pump output (terminal 21). Boiler sensor, outdoor sensor and DHW sensor are also shown in this layout. Power is 120 VAC, 60 Hz.

Pump exercise function

Viessmann · Vitocrossal 300 CA3B

Circulation pumps run for 10 seconds about once every 24 hours so they do not seize. This runs in all operating programs and during warm weather shutdown. Pumps can still seize during a long shutdown when they have no power, so the operator should reset the date and time after a prolonged shutdown.

Push-in DIN terminals in the junction box

Viessmann · Vitotronic 300 GW6B junction box

The junction box uses push-in terminals. Press the orange button before inserting or removing a wire. Terminal wire size is 26 AWG minimum to 12 AWG maximum. Ferrules help stop stranded wires fraying.

  1. Press the orange push-in button before inserting or removing a wire.
  2. Use wire from 26 AWG to 12 AWG.
  3. Use a ferrule on stranded wire to prevent fraying.

Push-in terminal use for accessory wiring

Viessmann · Accessory connections on the DIN rail

The DIN rail accessory terminals are push-in type and must be opened before inserting or removing a wire.

  1. Push in the orange button next to the terminal before installing or removing a wire.
  2. Use solid, stranded or stranded with ferrule wire. A ferrule helps prevent stranded wire from fraying.
  3. Use the top L, N terminal for pre-wired harness connections and the bottom L, N, G terminals for external equipment such as pumps or mixing valves.

Putting the control unit in maintenance position

Viessmann · Vitodens 222-F B2TB

The control unit can be moved to a different position if it is needed for commissioning or servicing.

Qualified contractor only

Viessmann · Vitotronic 200 and 300-K

Installation, adjustment, service and maintenance must be done by a licensed professional heating contractor. Owner or user must not service or adjust any part of the boiler, burner or control. The operator must have the boiler checked at least once a year, and defects must be fixed right away.

  1. Confirm the installer is a licensed heating contractor before any work.
  2. Leave all adjustments and repairs to the licensed contractor.
  3. Schedule an annual inspection before each heating season.

Quick heat-up and quick setback

Viessmann · Vitotronic 200-H HK1B with remote control and room temperature hook-up

Room set point changes of at least 2 K speed up heat-up or setback until the room reaches its new set point.

  1. For quick heat-up, raise the set room temperature by at least 2 K using party mode, a change from reduced to standard mode, or start optimisation (code B7).
  2. For quick setback, lower the set room temperature by at least 2 K using economy mode, a change from standard to reduced mode, or stop optimisation (code C1).
  3. Quick heat-up stops at the new set point; quick setback ends at the new set point.

Quick reference: Celsius to Fahrenheit conversion

Viessmann · Vitotronic 200-H, HK1S and HK3S

The back page has a Celsius to Fahrenheit quick reference table running from -40 °C (-40 °F) to +110 °C (+230 °F). Sample pairs: -40 °C = -40 °F, -18 °C = 0 °F, 0 °C = +32 °F, +10 °C = +50 °F, +20 °C = +68 °F, +30 °C = +86 °F, +60 °C = +140 °F, +100 °C = +212 °F.

  1. Find the Celsius value in the left column and read the Fahrenheit value beside it.

Raise reduced room temperature based on outdoor temperature

Viessmann · Heating circuit control

In reduced room temperature operation, the reduced setpoint can rise with outdoor temperature along the heating curve. It never goes above the standard room setpoint.

  1. Set the outdoor temperature at which raising starts in coding address F8.
  2. Set the outdoor temperature at which raising ends in coding address F9.
  3. Confirm the heating curve gives the expected room setpoint.

Raising reduced room temperature by outdoor temperature

Viessmann · Heating circuit reduced mode

During reduced room temperature operation the reduced setpoint can rise with outdoor temperature, following the heating curve, but never above the standard room setpoint.

  1. Set the outdoor temperature start limit for the raise at coding address F8.
  2. Set the outdoor temperature end limit for the raise at coding address F9.

Reach the main menu

Viessmann · Vitodens 100-W B1HE/B1KE

Start from the home screen. Every menu section (Heating, DHW, Faults, Information, Settings) is opened from the main menu. Some items only show on systems that have the matching feature, such as WiFi or a DHW recirculation pump.

  1. Tap the home screen to bring it up.
  2. Tap the menu button to open the main menu.
  3. Pick the section you need.

Read acknowledged fault messages

Viessmann · Vitotronic control unit

When a fault occurs, the red fault display flashes and shows the symbol and Fault. A connected central fault message facility is also triggered.

  1. Open the Faults list from the control unit.
  2. Check the fault messages, which are shown in red in date order.
  3. For a fault explanation, see the fault messages section of the manual.

Read boiler pressure and hot water temperature

Viessmann · Operating readings

Water pressure is shown on an analog gauge. Hot water temperature is shown continuously during operation.

  1. Read water pressure on the analog gauge.
  2. Read hot water temperature on the display during operation.

Read fault codes in BMS as hex text

Viessmann · Niagara AX or similar BMS reading gateway fault codes

Fault codes come from the gateway as decimal SNVT count values, while Viessmann controls show them in hex. In Niagara AX, a numeric bit-and mask can display the hex value, and a numeric-to-enum conversion can map the full range of Viessmann codes to text. Bound labels on a webpage can then show the text.

Read gas consumption

Viessmann · Vitocrossal 200 CI2

The boiler has an integral gas consumption meter. Readings are shown on the HMI and in ViGuide Web. DHW and heating circuit consumption are shown separately.

  1. Read current consumption, consumption for the past 7 days, current month, last month, current year and last year on the HMI or in ViGuide Web.
  2. Set the gas volume correction factor (parameter 1098.4) and the gross calorific value (parameter 1098.5) for accurate readings. Get these from the gas supplier or the gas bill.
  3. For lag boilers in ViGuide Web Pro, select the heat management unit (HMU) of the lag boiler.

Read or enter the service address

Viessmann · Vitocrossal 300 CA3B with Vitotronic 300 GW6C

Shows the heating contractor's details if they have been entered. If the field is empty, tap the white field to open the keypad and enter contact details.

  1. From the home screen, open Menu, then Information.
  2. Open Service address.
  3. If no details appear, tap the white field and enter them with the keypad.

Read system pressure from the pressure view

Viessmann · Vitotron 100 VLN2

The pressure view shows the installation pressure in psi. Use it to check the pressure before and after any service work. Pressure adjustments are for the authorized service person only.

  1. Press the pressure view button on the panel.
  2. Read the psi value on the display.
  3. If pressure is below 7 psi, have the system pressure raised by the authorized service person.

Read the boiler section status icons

Viessmann · Vitotronic 300 GW6C home screen

The header shows each boiler section's status. The flame symbol shows the current heating output. The circle symbol shows whether the section is running, available or unavailable.

  1. Flame with short length (1 to 33%): low heating output.
  2. Flame with medium length (34 to 66%): mid heating output.
  3. Flame with full length (67 to 100%): high heating output.
  4. Solid white circle: section is enabled by the system and lead control unit and is operating.
  5. Solid grey circle: section is available but not currently called for by the system and lead control unit.
  6. Crisscrossed circle: section is not available to generate heat.

Read the boiler status circles and output bars

Viessmann · Multi boiler cascade system, Vitotronic 300-K MW2C

The default display shows each boiler's state and its approximate heating output. The circle color and symbol show whether the boiler is enabled, idle or disabled.

  1. Blue circle: enabled by the cascade control and running.
  2. Gray circle: available to heat but not currently called by the cascade control.
  3. Circle with disable symbol: disabled for heat generation.
  4. A lead boiler symbol marks the lead boiler.
  5. Output bars show about 1-33%, 34-66% or 66-100% of heating output. The number under the circle shows the output in MBH or kW.

Read the boiler status symbols

Viessmann · Vitotronic 300-K default display

The flame symbol shows approximate current heating output. The circle shows whether a boiler is enabled, available or disabled.

  1. Flame with a short length: 1 to 33% output.
  2. Flame with a medium length: 34 to 66% output.
  3. Flame with full length: 66 to 100% output.
  4. Solid white circle: boiler is enabled by the cascade control and is running.
  5. Solid grey circle: boiler is available but has not been called by the cascade control.
  6. Crossed-out circle: boiler is disabled for heat generation.
  7. Read the value under the circle as current output in MBH or kW, depending on the selected measuring units (p. 23).

Read the default display

Viessmann · Vitotronic 300-K default display

The default display lists the installed boilers in boiler sequence order. Header shows the common supply temperature (actual and setpoint). Each boiler line shows its number, its operating mode, and its output.

  1. Check the common supply temperature actual and setpoint in the header.
  2. Check each boiler number, which is listed in boiler sequence order.
  3. Check the boiler symbol and its output value.
  4. To change the boiler sequence, see the Setting the Boiler Sequence section (p. 21).

Read the fault history (Vitotronic 200)

Viessmann · Vitotronic 200

The 10 most recent faults, including remedied ones, are saved and listed by date. The Vitotronic 200 menu path on this page is partly unreadable.

  1. Press OK and the second button together for about 4 seconds.
  2. Select Fault history.
  3. Select Display?.
  4. Press the exit button to leave.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.

Emergency Boiler Repair

647-657-2977