Viessmann Boiler: Opening the junction box and moving the control base to service position
Opening the junction box and moving the control base to service position on a Viessmann boiler: Access the wiring area of the control unit. Only needed when the programming unit is at the bottom.
Applies to: Vitodens 100-W B1HE/B1KE
How to fix opening the junction box and moving the control base to service position: step by step
- Discharge static by touching grounded metal such as a water pipe before starting.
- Release the tabs on the boiler control base.
- Pull the control base straight out.
- Place the control base in the service position, aligning its rear positioning tabs with the holes in the boiler jacket, and lock with the control base clips.
- Do not unplug the cable from the mounting panel.
- Do not change the position of the cable or its strain relief on the boiler jacket.
- Release the junction box cover clamps.
- Lift the junction box cover.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W B1HE/B1KE installation manual, p. 25. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.