Viessmann Boiler: Install the pressure relief valve and discharge pipe
Install the pressure relief valve and discharge pipe on a Viessmann boiler: Use the factory supplied approved pressure relief valve. Do not put an isolation valve between the boiler and the relief valve. The discharge pipe must be unthreaded, not reduced, and free of shutoff valves, and must run to a floor drain. Never pipe the discharge outdoors.
Applies to: Vitodens 200-W B2HA 80-100, 285-352
How to fix install the pressure relief valve and discharge pipe: step by step
- Install the factory supplied pressure relief valve.
- Do not install an isolation valve between the boiler and the relief valve.
- Run the discharge pipe, unthreaded, to a floor drain and end it about 6 in. (150 mm) above the drain.
- Keep the discharge pipe diameter at least 3/4 in. and do not reduce it.
- Place the discharge so it does not scald people nearby.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HA installation instructions, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.