Viessmann Boiler: Install pressure relief valve and discharge piping
Install pressure relief valve and discharge piping on a Viessmann boiler: Fit the factory pressure relief valve and drain valve with pipe sealant. The discharge pipe must go to a floor drain, not outdoors, and must not have a shutoff valve.
Applies to: Vitodens 200-W B2HB 19, 26, 35, 68, 94, 125
How to fix install pressure relief valve and discharge piping: step by step
- Remove the pressure relief valve, drain valve and fittings from the box.
- Apply pipe sealant to both ends of the fittings and install the tees.
- Install the pressure relief valve and the isolation valve, then tighten them.
- Pipe the discharge to a floor drain, ending about 6 in. (150 mm) above the drain.
- Use an unthreaded pipe end, and make sure there is no shutoff valve in the discharge line.
- Do not install an isolation valve between the boiler and the pressure relief valve.
- Position the discharge so it cannot scald people.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199
More commissioning tips for boiler
Source: Vitodens 200-W B2HB installation manual, p. 29. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.