Updated · by Aurora Star Tech Inc.

How the heating curve works on a Viessmann boiler: The lower the outdoor temperature, the higher the boiler water or supply temperature. Room temperature follows boiler water temperature. A different room setpoint shifts the curve parallel. The boiler water is raised above the required supply temperature by a set differential (factory 14.4°F / 8 K, coding address 9F). The supply temperature cannot exceed the boiler water temperature. Heating curve slope suits system type: low temperature (radiant floor) 0.2 to 0.7; medium temperature (cast iron, panel radiant floor) 0.7 to 1.2; high temperature (fin tube, fan coils) 1.2 to 1.5.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HA 80 to 100, 285 to 352

Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

More other tips for boiler

Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 39. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.