Viessmann Boiler: Enter service menu and actuator test
Enter service menu and actuator test on a Viessmann boiler: The service menu actuator test forces the burner to base load (low fire) or full load (high fire) for combustion checks.
Applies to: Vitodens 200-W B2HA 80 to 100 and 285 to 352
How to fix enter service menu and actuator test: step by step
- Press OK and the key shown on the page at the same time for about 4 seconds to enter the service menu.
- Select Actuator test.
- Select Base load OFF / ON for low fire, or Full load OFF / ON for high fire.
- Select 'all actuators off' to end the test.
- Press the exit key to leave the actuator test.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
B2HB 45B2HB 45, 160B2HB 57B2HB 57, 199B2HB 160B2HB 199
More service & test modes tips for boiler
Source: Vitodens 200-W B2HA 80 to 100, 285 to 352 Service Instructions, p. 30. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.