Updated · by Aurora Star Tech Inc.

Connecting the low-loss header sensor on a Viessmann boiler: The low-loss header sensor plugs into the X3 connector on the boiler control board. The X3 plug must be removed first to reach the terminals.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: Vitodens 200-W B2HB 19 to 35, 68 to 125

How to fix connecting the low-loss header sensor: step by step

  1. Remove the control unit cover.
  2. Remove the X3 plug from the control board.
  3. Connect the low-loss header sensor to terminals X3.4 and X3.5.
  4. Reinstall the X3 plug and control cover.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Viessmann Boiler codes

Models

Vitodens 200-W B2HB 45Vitodens 200-W B2HB 57Vitodens 200-W B2HB 160Vitodens 200-W B2HB 199

More other tips for boiler

Source: Vitodens 200-W B2HB 19 to 35, 68 to 125 Installation Instructions, p. 48. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.