Other: Boiler tips (part 11 of 45)
Short, practical technician tips on other for boiler. Check each one against the manual for your exact model before acting.
Coding 2 address map
Viessmann · Vitotronic 300-K, MW1S
Coding 2 addresses are grouped by function. Scrolling starts with system circuit A1, then mixing valve circuits M2 and M3, then the general and multi-boiler ranges.
- System circuit A1: addresses A0 to F2.
- Mixing valve circuit M2: addresses A0 to F2.
- Mixing valve circuit M3: addresses A0 to F2.
- DHW: addresses 54 to 75.
- General: addresses 76 to 9F and 40.
- General: addresses 4A to 4F.
- Multi-boiler control unit: addresses 41 to 49 and 35 to 3F.
Coding 8F changes apply on exit
Viessmann · Vitodens 200-W B2HA 80-100
Lockout (8F) only takes effect after you leave the service menu. Emissions test mode can be enabled when 8F is set to 1 or 2.
- Set coding 8F to the required lockout value.
- Exit the service menu.
- Confirm the lockout is active on the next menu access.
Coding changes take effect when the service menu is exited
Viessmann · Vitocrossal 300 CU3A coding
Some coding values, including 8F menu access, only become active after you leave the service menu.
- Make the coding change in the service menu.
- Exit the service menu to activate the change.
- Confirm the new setting works as expected.
Combustion air and carbon monoxide precautions
Viessmann · All Vitocrossal 200 CM2 units
The boiler needs fresh air for safe combustion. Installation and CO detector rules must be followed.
- Confirm adequate combustion and ventilation air according to the Mechanical room section of the installation instructions.
- Keep chemicals that produce poisonous combustion by-products out of the boiler room.
- Follow local regulations for carbon monoxide detector installation.
- Follow the Viessmann maintenance schedule.
Combustion air and installation location
Viessmann · Installation location and combustion air
The boiler needs clean combustion air. Corrosive chemicals and contaminated air can damage it.
- Do not install the boiler where chlorine, bromine, fluorine or other corrosive chemicals are stored, such as refrigerants, bleach, paint, thinner, hair spray, solvents or water softener salt.
- Avoid areas with excessive dust, high humidity or frost risk.
- Provide adequate ventilation and fresh combustion air.
- For oil-fired installs, follow CAN/CSA-B139 (Canada) or NFPA 31 (USA) and local codes.
- Size round combustion air ducts from outside using the methods in those codes.
Combustion air and ventilation openings
Viessmann · Vitocrossal 300 CA3B Series 2.5 to 6.0
Incomplete combustion and poisonous gases result if fresh air intakes in the mechanical room are closed.
- Confirm combustion air openings and ventilation air openings in the mechanical room are open.
- Never close or obstruct these openings.
- Keep the boiler room clear of combustible materials, gasoline and flammable vapors or liquids.
Combustion air blower power and protection
Viessmann · Combustion air blower power supply
Provide a disconnect and overcurrent protection for the 120 VAC blower supply as local codes require.
Combustion air supply for the boiler room
Viessmann · All fuel burning appliances including the hot water heating boiler
Tightly insulated homes can starve the boiler of combustion air, so the boiler room needs a fresh air supply.
- Provide a properly sized fresh combustion air supply to the boiler room.
- In tightly insulated homes, add a duct or opening for outside air.
- Follow applicable codes and instructions.
Combustion and ventilation air
Viessmann · Vitocrossal 300 CU3A 26 to 199
The boiler needs fresh combustion and ventilation air. Do not run it where the air is contaminated by dust, lint or chemicals, such as construction sites, garages, laundry rooms or near pools. Contaminated air can damage the boiler and cause property damage or injury.
- Confirm provisions for combustion and ventilation air exist in the mechanical room.
- Check the combustion air is free of dust, lint and chemicals before start-up.
- Keep chemicals that can contaminate the air out of the boiler room.
Combustion chamber door and side clearance
Viessmann · Vitorond 200 VD2 boilers
The door can swing left or right to reduce side clearance.
- The combustion chamber door hinges on the left from the factory.
- Rebuild the door hinge hardware to change to a right-hand hinge.
- Keep at least 20 in. (500 mm) side clearance for side-mounted Vitotronic controls.
Comfort adjustments for occupants
Viessmann · Vitocrossal 200 CI2 weather-compensated and constant operation
Set the preferred room temperature and adjust time programs so the preferred temperature is reached when occupied. In weather-compensated operation, heating curves can be adjusted for year-round comfort. Extended heating gives a higher room temperature short term. One-off DHW heating gives extra hot water for a short time. Remote control units, if installed, can also adjust some settings.
- Set the preferred room temperature on the heating circuit display.
- Adjust heating curves only in weather-compensated operation.
- Use Extended heating for a short-term higher room temperature.
- Use one-off DHW heating for a short-term higher DHW temperature.
Common venting limitation
Viessmann · B2HB 45, 57, 160, 199
The Vitodens 200-W can only be common vented with other Vitodens 200-W boilers of the same size and series. Refer to the Common Venting Manual for details.
- Confirm that all boilers on the common vent are the same size and series before connecting.
Compiled fault indicator alarm connection
Viessmann · Vitotronic 300 KW3
A visual and/or audible alarm can be wired to the Power Pump Module. Alarm rating is 120 VAC, 60 Hz, 3 FLA.
- Connect the alarm wires to the matching terminals on the Power Pump Module (L, G, N).
Condensate and venting notes
Viessmann · Vitocrossal 200 CM2 186 to 620
Condensate pH is about 3 to 4 (the venting section gives 3 to 5.5). Flue gas temperatures can range from 77°F (25°C) to 257°F (125°C) depending on boiler water temperature. Condensate can drain to a floor drain. If local rules require neutralizing, a correctly sized neutralization tank is needed. Treated condensate should reach pH 6.5 to 9 before disposal. The vent system must be designed by the chimney or venting manufacturer.
- Confirm local requirements for neutralizing condensate before disposal.
- Use a neutralization tank sized by Viessmann if neutralizing is required.
- Confirm treated condensate is pH 6.5 to 9 before disposal to waste water.
Condensate disposal
Viessmann · All CM2 models
Condensate is acidic and may need neutralizing before drain disposal.
- Dispose of condensate into a floor drain, collecting chimney condensate with it if desired.
- If local rules require neutralizing, use a correctly sized neutralization tank from Viessmann.
- Confirm treated condensate reads pH 6.5 to 9 before disposal into the waste water system.
Condensate drain back in vent
Viessmann · Two-pipe and single-pipe vent layouts
Condensate from the vent can drain back to the boiler.
- Plan the base of the vent so condensate can drain back to the boiler.
- A base tee may be replaced with an elbow where shown in the venting options.
Condensate drain installation rules
Viessmann · Vitodens 200-W B2HA 80 to 100 and 285 to 352
Vent the drain between the condensate trap and the neutralization unit where one is fitted. Do not connect drains from other appliances such as a water softener backwash into the Vitodens condensate drain.
- Confirm the drain is open or vented to a field drainage system.
- Make sure the drain pipe between the trap and the neutralizer is vented.
- Do not tie in other appliance drains.
Condensate pH and disposal
Viessmann · Vitocrossal 300 CA3B
Condensate from this condensing boiler is acidic. Local rules may require neutralising it before drain disposal. Neutralised condensate should reach a pH of about 6.5 to 9.
- Check local building requirements before disposing of condensate.
- If neutralising is required, use a correctly sized neutralisation tank from Viessmann.
- Dispose of condensate into a floor drain or wastewater system only after neutralising where required.
Connect control unit to LON system
Viessmann · Vitotronic 200-H with LON system
If used, the LON system cable plugs into the LON connection on module A2. Data transfer over LON can take several minutes.
- Plug the LON system cable into the LON connection on module A2.
- Allow several minutes for data transfer before judging the connection.
Connect external dry contacts safely
Viessmann · Digital inputs DE1 to DE3
External contacts on DE1 to DE3 must be floating. Keep the required spacing from live parts.
- Use floating (dry) contacts only.
- Keep 8.0 mm air and creep path, or 2.0 mm insulation thickness, from live parts (safety category II).
- Only assign one function to each connection.
Connect the DHW tank temperature sensor
Viessmann · Vitodens 200-W B2HA 80-100, 285-352
The DHW sensor plugs into the quick connect plugs from the boiler control board (connector X9). Install the sensor in the tank as described in the storage tank instructions.
- Attach the DHW sensor to the quick connect plugs from the control board (X9).
- Install the sensor in the DHW tank per the Vitocell instructions.
Connecting a 24 VAC thermostat
Viessmann · Vitodens 222-F, B2TB 19, 35, 68, 125
A potential-free (dry) T-T contact from a switching relay connects to the EA1 module in the boiler junction box. With the contact closed, burner operation depends on load and heats the supply water to the value set in coding address 9b. Live contacts cause short circuits or phase failure, so the external connection must be potential-free. With only a thermostat controlling room temperature, the standard and reduced room set points can be set to 37 ºF (3 ºC) to reduce cycling.
- Connect the normally open dry contact of the switching relay (T-T) to terminal DE1, DE2 or DE3 of the EA1 module in the boiler electrical junction box.
- Connect the switching relay to the thermostat and power supply per the manufacturer's instructions.
- Set coding addresses 3A, 3B or 3C in the General group to 2.
- Set coding address 9b in the General group to the required supply water limit.
- If the thermostat is the only room control, set the standard and reduced room set points to 37 ºF (3 ºC).
Connecting the DHW tank temperature sensor
Viessmann · Vitodens 200-W B2HB 45, 57, 160, 199
The DHW sensor plugs into the quick connect plugs on the boiler control board. The sensor itself is installed per the Vitocell instructions supplied with the DHW tank. System coding information is in the Service Instructions.
- Attach the DHW sensor to the quick connect plugs from the boiler control board (X9 connector).
- Install the DHW tank temperature sensor as described in the Vitocell Installation Instructions.
Connecting the low-loss header sensor
Viessmann · Vitodens 200-W B2HB 19 to 35, 68 to 125
The low-loss header sensor plugs into the X3 connector on the boiler control board. The X3 plug must be removed first to reach the terminals.
- Remove the control unit cover.
- Remove the X3 plug from the control board.
- Connect the low-loss header sensor to terminals X3.4 and X3.5.
- Reinstall the X3 plug and control cover.
Connection overview
Viessmann · Versatronik 200 control
Terminal blocks are grouped by function: sensor low voltage (1 to 13), 0-10 VDC input, CAN BUS (H, L, -, +), 120 VAC power in (N, L), 120 VAC pump outputs (24, 25, 26, 36, 37), ground strip, dry-contact burner demands (29, 30, 32, 33), and mixing valve terminals (27, C, 28 and 34, C, 35) with a coding card.
- Identify the terminal group before wiring.
- Use the coding card for the mixing valve connections.
- Keep sensor wiring away from 120/240 VAC conductors.
Constant and weather-compensated heating operation
Viessmann · Vitodens 100-W B1HE/B1KE
In constant operation the boiler holds a fixed supply temperature regardless of outside temperature. In weather-compensated operation the supply temperature follows the outside temperature, so more heat is supplied as it gets colder. The outside temperature is read by a sensor mounted outside the building. The contractor selects the mode at commissioning.
- Check with the contractor which operating mode was set at commissioning.
Contaminated combustion air
Viessmann · Vitocrossal 300 CU3A 26 to 199
Do not run the boiler where combustion air is contaminated by dust, lint or chemicals. Such air damages the boiler and can cause serious harm.
- Check that the boiler room air is free of dust, lint and chemicals.
- Keep the boiler away from construction sites, garages, workshops, laundry areas, pools and manufacturing areas.
- Have the boiler inspected and serviced at least once a year.
Control applicability
Viessmann · Vitotronic 100 GC1 and Vitotronic 300-K MW1S
Both control units are only for integration and installation on Viessmann boilers and for control panel mounting. The Vitotronic 100 GC1 has no LON module fitted as standard; its LON module is supplied with the control panel. The Vitotronic 300-K MW1S has an integral LON module.
Control board fuse ratings
Viessmann · Vitotronic 200 KW2
Fuse F1 on the rear of the control is T6.3 A (heating system on/off switch circuit). Fuse F2 on the mother board is T4 A (adjustable high limit circuit).
- Replace F1 only with a T6.3 A fuse.
- Replace F2 only with a T4 A fuse.
Control is not a temperature limit safety device
Viessmann · Versatronik 10.WB1 with Viessmann Vitodens 100-W WB1A and WB1B
This control does not replace a temperature limit. Where required, install a separate mechanical or electrical safety device.
- Check whether local rules require a separate limit device on the system.
- Install that device separately if it is required.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.