Viessmann Boiler: Clocking the natural gas meter to verify burner input
Clocking the natural gas meter to verify burner input on a Viessmann boiler: Time the meter to calculate the boiler input in Btu/h and confirm it is correct. A boiler under-fired by 5% is acceptable. Do not over-fire the boiler.
Applies to: Gas meter verification
How to fix clocking the natural gas meter to verify burner input: step by step
- Contact the gas utility for the correct heating value before timing the meter.
- Turn off all other gas appliances served by the meter.
- Time how many seconds the boiler takes to use 10 cu ft of gas.
- Divide 3600 times 10 by the seconds to get cu ft per hour, then multiply by the heating value to get Btu/h input.
- Example: 240 seconds at 1000 Btu/cu ft gives 150,000 Btu/h, which is correct for a Vitodens 100-W 150.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.