Viessmann Boiler: Checking the expansion tank and system pressure
Checking the expansion tank and system pressure on a Viessmann boiler: Set the expansion tank precharge and the system fill pressure with the system cold, then record the minimum fill pressure.
Applies to: Site expansion tank and system
Common causes of checking the expansion tank and system pressure
- Low water pressure from leakage shows up as a lower gauge reading
How to fix checking the expansion tank and system pressure: step by step
- Drain the boiler/system and reduce pressure until the gauge reads 0.
- If the tank nitrogen precharge is below the system static pressure, inflate the membrane to slightly above system pressure.
- Top up with water until fill pressure is higher than the expansion tank inlet pressure. With the system cold, fill pressure should be about 3 psig above static pressure.
- On first start-up, mark this reading as the minimum fill pressure on the gauge.
- Repair all leaks. A lower gauge reading later usually means water loss.
- Do the check with the system cold, with tank pressure matched to system fill pressure at about 60 F (15.6 C).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.