Viessmann Boiler: Checking combustion quality (CO2 or O2 and CO)
Checking combustion quality (CO2 or O2 and CO) on a Viessmann boiler: Test CO2 or O2 and CO at the lower and upper heating output. Allow about 50 seconds after start before testing, since the controller calibrates itself.
Applies to: Natural gas and LPG
Common causes of checking combustion quality (co2 or o2 and co)
- CO2 or O2 outside the permissible range, which can point to a flue leak or a faulty ionization electrode or cable
How to fix checking combustion quality (co2 or o2 and co): step by step
- Connect a flue gas analyzer at flue gas port A on the boiler flue connection.
- Open the gas shut-off valve, start the boiler and create a call for heat.
- Set the lower heating output, then check CO2 and record it.
- Set the upper heating output, then check CO2. If it is more than 1% outside the range, correct it.
- Record the values, then re-seal test port A.
- If values are out of range, check the flue system for leaks (p. 49) and the ionization electrode and cable (p. 51).
- Check test port A for leaks. Escaping flue gas is harmful.
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
Source: Vitodens 100-W B1HE/B1KE Combi Installation/Service, p. 59. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.