Viessmann Boiler: Check flue gas temperature sensor and fixed high limit
Check flue gas temperature sensor and fixed high limit on a Viessmann boiler: Use the resistance curves to check the flue gas sensor. If the boiler cannot be reset after an F2 shutdown while water is below about 203°F (95°C), check the fixed high limit.
Applies to: Vitodens 100-W WB1B
How to fix check flue gas temperature sensor and fixed high limit: step by step
- Pull the leads from the flue gas temperature sensor and check its resistance against the curve; replace it if the deviation is severe.
- Pull the leads from the fixed high limit and check continuity with a multimeter.
- Replace the fixed high limit if it has no continuity.
- Coat the new fixed high limit with heat conducting paste and install it.
- Reset the control (see page 76).
If the unit shows an error code, look it up: Viessmann Boiler codes
Models
More service & test modes tips for boiler
Source: Vitodens 100-W WB1B installation and service instructions, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.