Viessmann Boiler: CAN bus subscriber numbers and electronics modules
CAN bus subscriber numbers and electronics modules on a Viessmann boiler: When troubleshooting, note the subscriber number shown with the fault and check that component. Modules: A = BCU burner control unit, B = HMU heat management unit with wiring panel, C = HMI programming unit with WiFi module.
Applies to: Vitodens 100-W B1HE/B1KE
How to fix can bus subscriber numbers and electronics modules: step by step
- Subscriber 1: HMU heat management unit.
- Subscriber 50: BCU burner control unit.
- Subscriber 58: communication module (TCU 200).
- Subscriber 59: HMI programming unit.
- Subscriber 60: fan unit.
- To find the module, check the rotary switch S1 on the module if needed.
If the unit shows an error code, look it up: Viessmann Boiler codes
Source: Vitodens 100-W B1HE/B1KE installation/service manual, p. 69, 71. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.