Rinnai Boiler: Wire DHW recirculation pump
Wire DHW recirculation pump on a Rinnai boiler: External recirculation pump connects to the Pump 4 terminal on the PC board when DHW recirculation is used. If four CH zone pumps are used, an external CH zone controller is required.
Applies to: I-Series Plus Condensing Combi Boiler
How to fix wire dhw recirculation pump: step by step
- Wire the external recirculation pump to the Pump 4 terminal on the PC board.
- If four CH zone pumps are used, add an external central heating zone controller.
- Set Parameter 09 to b (ON) to enable recirculation.
- Use an optional 24 V timer if timed recirculation is needed.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 99. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.