Vent termination location rules on a Rinnai boiler: Terminations must be at least 12 in. above ground or the expected snow level. Keep them away from dryer vents, commercial cooking exhaust and air inlets. Do not terminate over public walkways, near soffit or crawl space vents, or where condensate or vapour could cause a nuisance, damage, or harm regulators or relief valves. Under a soffit or eave, keep exhaust out of soffit vents, keep it clear of where moisture collects, and do not place it so close that exhaust recirculates into the combustion air intake. Local code can be stricter than these clearances. Category IV horizontal runs must slope up at least 1/4 in. per foot toward the terminal, prevent condensate pooling, and provide drainage where needed.
Applies to: I-Series Plus vent terminations
How to fix vent termination location rules: step by step
- Confirm the termination is at least 12 in. above ground or expected snow level.
- Check the location against dryer vents, commercial cooking exhaust and air inlets.
- Avoid walkways, soffit and crawl space vents, and areas where condensate or vapour can cause damage.
- Under eaves, check exhaust cannot enter soffit vents or recirculate into the combustion air intake.
- Slope Category IV horizontal runs up at least 1/4 in. per foot toward the terminal and provide drainage for condensate.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 23. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.