Rinnai Boiler: Test the ignition safety shutoff device

Updated · by Aurora Star Tech Inc.

Test the ignition safety shutoff device on a Rinnai boiler: Simulates a flame loss by disconnecting the flame rod. The boiler should lock out with code 110 after the last start-up attempt.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: All I-Series Plus condensing combi boilers

How to fix test the ignition safety shutoff device: step by step

  1. Make sure the boiler is not firing and the flame rod is not hot.
  2. Remove the boiler front panel.
  3. Disconnect the wiring connection from the left side flame rod under the burner. Do not touch the inside of the connector.
  4. Call for heat or turn on a DHW fixture to start the boiler.
  5. Confirm the boiler makes one start-up attempt and several restart attempts, then locks out with code 110 and the gas valve shuts off.
  6. Reconnect the flame rod wiring, press the DHW button to reset, and replace the front panel.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Rinnai Boiler codes

Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 123. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.