Rinnai Boiler: Room air multiple boiler vertical termination
Room air multiple boiler vertical termination on a Rinnai boiler: Exhaust termination spacing for room air installations with multiple boilers.
Applies to: Room air venting with multiple boilers
How to fix room air multiple boiler vertical termination: step by step
- Use only listed Category IV venting for room air installations.
- Place all terminations (horizontal and/or vertical) at least 12 in above grade or anticipated snow level.
- Keep 12 in (0.30 m) minimum clearance from the roof to the termination.
- Keep 60 in (1.52 m) vertical spacing between terminals.
- Keep 12 in (0.30 m) clearance from the inside corner.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.