Rinnai Boiler: Piping with refrigeration, air handler coils and multiple zones
Piping with refrigeration, air handler coils and multiple zones on a Rinnai boiler: Requirements for installations where the boiler is near cooling equipment or has several zone valves.
Applies to: Chilled water and multi-zone piping
How to fix piping with refrigeration, air handler coils and multiple zones: step by step
- When the boiler is used with a refrigeration system, pipe the chilled medium in parallel with the boiler and use valves so chilled medium cannot enter the boiler.
- If the boiler feeds heating coils in air handlers exposed to refrigerated air, fit flow control valves or another automatic method to stop gravity circulation during cooling.
- If there are multiple zone valves, a differential bypass may be needed to prevent excessive flow through one zone when the other zones are closed.
- Expect water to come out when plastic sealing caps are removed from the boiler connections, because of live fire testing at the factory.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 57. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.