Rinnai Boiler: Manual CH plumbing flush and purge
Manual CH plumbing flush and purge on a Rinnai boiler: Flush the heating system with approved cleaner before adding a new boiler when replacing an existing one. Clean the dirt trap, then purge the boiler and system.
Applies to: All I-Series Plus condensing combi boilers
Common causes of manual ch plumbing flush and purge
- Scale and sludge in the heating system
How to fix manual ch plumbing flush and purge: step by step
- Disconnect power and turn off gas.
- Add an approved cleaner and follow its directions. Run the boiler in DHW or heating for 3 days.
- Flush the boiler and system and clean the dirt trap.
- Add an approved inhibitor (recommended).
- Purge the system: close supply shutoff #3 and boiler valves #1 and #2, open autofill to at least 20 PSI, then flush through hose #2 with boiler drain #4 open.
- Purge the boiler: keep valves #1 and #3 closed, open #2, close #4, and flush through hose #1 with autofill at least 20 PSI.
- Continue purging until no bubbles show in the bucket.
- Run the boiler in its deaeration program per the deaeration section.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus Condensing Combi Boiler Manual, p. 121. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.