Rinnai Boiler: Convert the boiler from natural gas to propane
Convert the boiler from natural gas to propane on a Rinnai boiler: The boiler is set up for natural gas only from the factory. Conversion must be done by a qualified service agency using the conversion kit instructions and local codes. Check the inlet gas pressure before you start.
Applies to: I-Series Plus condensing combi boiler
How to fix convert the boiler from natural gas to propane: step by step
- Confirm the inlet gas pressure is between the minimum and maximum allowed for this boiler.
- Shut off the gas supply before disconnecting electrical power.
- Locate the PC board (lower left of the unit) and the left PC board button.
- Press and hold the left PC board button for five seconds. 00-A appears.
- Scroll to parameter AO and press Select.
- Press the up or down arrow to choose the gas type, then press Select.
- Once the setting is complete, press the left PC board button to return to normal operation.
- Fit a new conversion label to the boiler showing the gas type.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, pp. 131-132. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.