Rinnai Boiler: Condensate drain line installation
Condensate drain line installation on a Rinnai boiler: The boiler has an integrated condensate trap and the drain must be installed to prevent damage and freezing.
Applies to: Condensate drain piping
How to fix condensate drain line installation: step by step
- Use only corrosion-resistant drain materials such as PVC pipe or plastic hose.
- Keep the drain pipe at least the same diameter as the 1/2 in MNPT drain connection along its whole length.
- Slope the drain toward the floor drain or condensate pump. Keep the pipe as short as possible with a downward pitch.
- Leave the drain end open to the atmosphere, not under water or other substances.
- Wrap drain lines in freezing areas with an approved heat source, installed per its maker's instructions.
- For outdoor installations, run the drain through an interior wall or between insulation and an interior wall to reduce freezing.
- Install a condensate pump if no floor drain is available or the drain is above the condensate drain outlet.
- Dispose of condensate according to local codes. Use a neutralizer kit where local code requires it.
- Do not install an external condensate trap, because the boiler has one built in.
- Do not connect the condensate drain to an air conditioning evaporator coil drain.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 60. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.