Rinnai Boiler: Common vent spillage test when a boiler is removed
Common vent spillage test when a boiler is removed on a Rinnai boiler: Required by ANSI Z21.13 when an existing boiler is taken off a common vent. The remaining appliances on the vent must be checked to confirm they still vent safely.
Applies to: Boilers on common vent systems
Common causes of common vent spillage test when a boiler is removed
- Common vent may be oversized for the remaining appliances once the boiler is removed
How to fix common vent spillage test when a boiler is removed: step by step
- Seal any unused openings in the common vent system.
- Inspect the vent for correct size, horizontal pitch, blockage, leakage and corrosion.
- Close building doors, windows and doors to other spaces. Run clothes dryers and non-vented appliances, and run exhaust fans such as range hoods and bathroom fans at full speed. Do not run a summer exhaust fan. Close fireplace dampers.
- Light the appliance under test and run it continuously.
- After five minutes of main burner operation, check for spillage at the draft hood relief opening with a match, candle or smoke.
- After testing, restore doors, windows, fans, dampers and other gas appliances to their previous state.
- Correct any improper venting so it meets NFPA 54 / ANSI Z223.1 or CAN/CSA B149.1, resizing toward the minimum size from the code tables.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 140. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.