Rinnai Boiler: Combustion air requirements for confined and unconfined spaces
Combustion air requirements for confined and unconfined spaces on a Rinnai boiler: Sizing rules for combustion air openings based on the appliance Btu input.
Applies to: Combustion air supply for all installations
How to fix combustion air requirements for confined and unconfined spaces: step by step
- Treat the space as unconfined if its volume is at least 50 cubic feet per 1000 Btu/hr of total appliance input. Tight buildings may still need outside air.
- Treat the space as confined if its volume is less than 50 cubic feet per 1000 Btu/hr. A confined space needs two combustion air openings.
- For indoor air from joining rooms, provide at least 1 sq in of free area per 1000 Btu/hr, minimum 100 sq in per opening.
- For outdoor air through horizontal ducts, provide at least 1 sq in per 2000 Btu/hr of total input (1100 mm² per kW).
- Place the upper opening within 12 in (0.30 m) of the top and the lower opening within 12 in (0.30 m) of the bottom. Keep the openings unobstructed.
- If duct cross section is used, it must be at least equal to the required free area.
- Assume wood louvers give 25% free area and metal louvers or grills give 75%. Do not use openings smaller than 1/4 in.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 42. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.