Rinnai Boiler: Choose a vent termination location
Choose a vent termination location on a Rinnai boiler: Termination clearances for concentric and twin pipe venting. Exact clearances are in the vent clearance setting. Local codes and the gas supplier can override these.
Applies to: Concentric and twin pipe terminations
How to fix choose a vent termination location: step by step
- Place all horizontal and vertical terminations at least 12 in (0.30 m) above grade or the anticipated snow level.
- Keep 60 in (1.52 m) between terminals at the same level and 60 in vertically between terminals at different levels.
- For twin pipe multi-boiler vertical venting, keep the exhaust at least 12 in (0.30 m) above the combustion air opening.
- Keep the combustion air intake out of the area marked as not permitted in the sidewall diagram.
- Check the clearance to windows, doors, air inlets, soffits, corners and walkways against the clearance setting.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 37-38, 40. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.