Rinnai Boiler: Central heating return and supply connections
Central heating return and supply connections on a Rinnai boiler: Connect the heating circuit to the two bottom connections of the boiler. Purge the system first, because debris and air in the lines will damage the boiler. Piping must follow state and local plumbing codes.
Applies to: Heating return and supply connections
How to fix central heating return and supply connections: step by step
- Connect the heating return line to the heating return connection on the bottom of the boiler.
- Connect the heating supply line to the heating supply connection on the bottom of the boiler.
- Purge the heating system of all debris and air before connecting the boiler.
- Install an air separator on the central heating supply side.
- Insulate system piping where freezing is a possible concern.
- Do not connect the boiler directly to a system that uses polybutylene or other oxygen-permeable piping.
- If oxygen-permeable tubing is used, install a plate heat exchanger to isolate the tubing from the boiler.
- Use hydraulic separation with primary/secondary piping when connecting the water supply.
If the unit shows an error code, look it up: Rinnai Boiler codes
Source: Rinnai I-Series Plus IP060160C installation and operation manual, p. 57-58. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.