Navien Boiler: Wiring a zone valve system
Wiring a zone valve system on a Navien boiler: Zone valves are powered from the boiler's 24 VAC supply, which is limited by the 75 VA transformer.
Applies to: NCB700 zone valve systems
How to fix wiring a zone valve system: step by step
- Connect each zone valve to the boiler through its COM and NO or NC terminal, as set by the valve type.
- NO (normally open): valve power is on while the valve is operating and turns off when it stops.
- NC (normally closed): valve power is on while the valve is stopped and turns off when it operates.
- Connect the system pump to the Zone Pump 3 terminals. The system pump must be on those terminals in zone valve systems.
- Keep the total zone valve draw at or below 72 VA. If it is higher, add an external zone valve controller.
- For Taco 570/571 and Taco Sentry valves, connect zone valve 1 to boiler COM and zone valve 2 to boiler NO.
- For thermostats with their own 24 VAC power, wire each thermostat input with its 24 VAC neutral and line.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 44, 45, 46. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.