Navien Boiler: Wiring a 3-zone zone pump system
Wiring a 3-zone zone pump system on a Navien boiler: Dry contact zone pumps, with or without 24 VAC thermostat power, plus optional DHW recirculation.
Applies to: NCB700 zone pump systems
How to fix wiring a 3-zone zone pump system: step by step
- Wire each zone pump's line and neutral to its own zone pump terminal on the boiler (zone pumps 1 to 3, each max. 2.5 A).
- Connect the boiler external pump to its terminal if one is used (max. 2.5 A). The boiler internal pump uses its own terminal.
- For a 24 V thermostat, connect it to the R and C terminals on the boiler PCB. Use C only when the thermostat has a COMMON wire.
- For thermostats with their own 24 VAC power, wire the thermostat input, 24 VAC neutral and 24 VAC line to each thermostat input.
- For DHW recirculation, use a recirculation timer, aquastat or HotButton push button, and select external recirculation in the DHW recirculation menu.
- For combi pre-heat, skip the recirculation pump and select combi pre-heat in the DHW recirculation menu.
- If the DHW recirculation menu is set to Always On, Intelligent or Weekly, no aquastat or extra HotButton is needed.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 40, 41, 42, 43. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.