Navien Boiler: Termination resistor DIP switch
Termination resistor DIP switch on a Navien boiler: Enable termination only if the gateway is the last device on the serial trunk. Termination also overrides bias resistors if both are connected.
Applies to: R1 and R2 ports
How to fix termination resistor dip switch: step by step
- If the gateway is the last device on the trunk, move the TERM DIP switch to the right on the port in use.
- Leave termination off for gateways in the middle of the trunk.
- Power cycle the gateway after changing the switch, since changes do not apply while powered.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien Modbus/BACnet gateway installation and operation manual, p. 9. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.