Navien Boiler: Measuring inlet gas pressure
Measuring inlet gas pressure on a Navien boiler: Procedure to measure the gas inlet pressure at the boiler under maximum firing. Only a licensed professional should do this.
Applies to: NCB700 gas pressure check
How to fix measuring inlet gas pressure: step by step
- Close the manual gas valve in the supply line.
- Turn on the boiler. On the front panel, press the Back button and the Menu button together for 3 seconds, then turn the dial to select '7. Special Operations'.
- Press the dial to enter special operation mode.
- Turn the dial to select '7. SH 2nd MAX (CL 2e MAX)' and press the dial to select the mode.
- Press the Back button twice to return to normal operation.
- Run space heating so the gas in the supply line is purged.
- Let the boiler run until it shuts off from lack of gas, then turn the boiler off.
- Remove the 4 front cover screws (2 top, 2 bottom) with a Phillips screwdriver to access internal components.
- Loosen the screw shown in the manual and connect a manometer to the pressure tap on the outlet side. Zero the gauge before use.
- Reopen the manual gas valve and check for leaks.
- Open several domestic hot water taps at maximum temperature to bring the boiler to maximum firing rate.
- Run all other gas appliances in the house. At maximum firing, read the inlet pressure on the manometer.
- Compare the reading with the inlet pressure limits (see the gas pressure setting in this section).
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation & operation manual, pp. 227-229. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.