Navien Boiler: Installing the condensate siphon loop on a cascade system
Installing the condensate siphon loop on a cascade system on a Navien boiler: The condensate drain forms a siphon loop that must be primed with water before the boiler runs.
Applies to: NCB700-190/060, NCB700-190/080, NCB700-240/110, NCB700-240/130, NCB700-250/150
How to fix installing the condensate siphon loop on a cascade system: step by step
- Form a loop in the field-supplied drain hose and secure it with a tie. Do not kink the hose or tie it too tight.
- Prime the loop with tap water. Water in the hose must be above 7.9 in (200 mm) and must be present before the boiler runs.
- Connect the hose to the cascade system and route the end to a drain.
- Check that the loop still holds water before each operation.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 103. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.