Navien Boiler: Installing the condensate neutralizer kit
Installing the condensate neutralizer kit on a Navien boiler: A Navien neutralizer kit is recommended when condensate goes through a neutralizing agent. Flue gases must never pass through the neutralizer. Only one appliance may connect to each neutralizer.
Applies to: NCB700 condensate neutralizer kit
How to fix installing the condensate neutralizer kit: step by step
- Mount the neutralizer on a wall or floor with the brackets in the kit.
- Keep the neutralizer inlet and discharge closer to the floor than the condensate drain.
- Horizontal mounting: rotate so the outlet is at the highest point.
- Vertical mounting: keep the outlet higher than the inlet.
- Install an overflow bypass between the appliance and the neutralizer to stop backflow.
- Use corrosion-resistant piping and secure it so it cannot move.
- Use a Y-fitting for extra safety if the condensate drain blocks, and confirm the condensate still runs freely to the drain.
- Keep the discharge connection accessible for maintenance and pH testing.
- Fill the trap by pouring water into the boiler's exhaust vent until water runs through the condensate drain.
- Keep piping away from freezing temperatures and protect it from pedestrian damage and vibration.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 27. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.