Navien Boiler: Installation checklist: gas, water, heating and relief valve
Installation checklist: gas, water, heating and relief valve on a Navien boiler: Gas, domestic water, space heating and pressure relief items to confirm before commissioning.
Applies to: NCB700 installation
How to fix installation checklist: gas, water, heating and relief valve: step by step
- Confirm gas type matches the rating plate. Confirm gas line is at least 1/2 or 3/4 in ID and long enough for the BTU load.
- Measure gas supply pressure and confirm it is within the manual's range.
- Confirm a manual shut-off valve is on the gas line, and test the line and fittings for leaks.
- Confirm domestic water supply pressure is greater than 40 psi.
- Install shut-off valves on inlet and outlet for filter cleaning, bleed air at each fixture, and clean the inlet water filter.
- Insulate hot water and return lines if a recirculation line is used.
- Confirm the system is filled to under 30 psi and purged of air.
- Confirm air removal means are in the piping, and that an expansion tank is set to the correct system pressure.
- If propylene glycol is used, confirm type and concentration.
- If an external low water cut-off is used, confirm it is wired to the boiler.
- Confirm an approved pressure relief valve is on the top of the boiler, rated at or above the boiler BTU input, and 3/4 in on the space heating outlet.
- Run a discharge tube from the relief valve to within 6 to 12 in (150 to 300 mm) of the floor.
- Install a condensate drain line to a drain or laundry tub, and check the condensate pump if one is used.
If the unit shows an error code, look it up: Navien Boiler codes
More commissioning tips for boiler
Source: Navien NCB700 installation and operation manual, p. 107-108. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.