Navien Boiler: Install the heating system relief valve
Install the heating system relief valve on a Navien boiler: Install the relief valve vertically on the boiler outlet through the universal adapter, with a vent on the adapter. The valve must be ASME approved.
Applies to: NCB700 space heating system
How to fix install the heating system relief valve: step by step
- Connect the universal adapter to the RAL adapter on top of the boiler
- Install the relief valve and a vent on the universal adapter
- Check that the relief valve capacity is at least the maximum heating system pressure
- Check that the valve's BTU/H rating is at least the boiler's maximum input
- Run the discharge pipe so hot water cannot spray the operator or equipment
- Terminate the discharge pipe 50 to 150 mm (2 to 6 in) above the floor or floor drain so the discharge is visible
- Keep the discharge pipe free of valves, reducers and blockages
- Do not install any other valve between the relief valve and the boiler
- After filling and pressurizing, test the valve by lifting the lever; replace the valve right away if it does not work
- Test the valve manually at least once a year
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 184-185. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.