Navien Boiler: Indoor vent termination clearances
Indoor vent termination clearances on a Navien boiler: Clearances for two-pipe, concentric and low-profile indoor venting. The exhaust and intake terminations must stay apart, and concentric sidewall terminations must not be stacked.
Applies to: Indoor boiler installs, sidewall and vertical venting
How to fix indoor vent termination clearances: step by step
- Keep at least 12 in (300 mm) between the intake and exhaust terminations for non-concentric sidewall and vertical venting.
- Keep the intake and exhaust at least 12 in (300 mm) from any obstruction above, below, left or right.
- Keep the termination at least 12 in (300 mm) above the highest expected snow level or grade, or as local code requires, whichever is greater.
- For concentric vertical venting, do not go above 24 in above the roof.
- For cascade installs, keep 12 in horizontal clearance between terminations for both sidewall and vertical venting.
- Do not vertically stack concentric terminations on sidewalls. Exhaust recirculation will cause bad boiler operation.
- For twin-pipe terminations, use only the allowed orientations. Never put the exhaust nearest the ground.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 73-75. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.