Navien Boiler: Indirect venting and negative pressure
Indirect venting and negative pressure on a Navien boiler: With indirect (single-pipe) venting, the room can go under negative pressure, which can push cold air back through the heat exchanger and cause freezing and malfunction. Building codes generally forbid negative pressure in homes. If there is any doubt, use direct venting instead. The page 240 text warns that freeze damage caused by backdraft is not covered by the manufacturer warranty.
Applies to: NCB700 indirect (single-pipe) venting
How to fix indirect venting and negative pressure: step by step
- Insert the vent outlet plug into the air intake pipe for indirect venting. Do not glue it so it can be removed and cleaned.
- Check the room air supply is balanced and the space cannot go under negative pressure.
- If negative pressure is possible or in doubt, switch to direct venting.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 240. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.