Navien Boiler: Gas orifice change for LP or high altitude
Gas orifice change for LP or high altitude on a Navien boiler: Procedure to swap the gas orifice and convert the boiler.
Applies to: NCB700 gas conversion
How to fix gas orifice change for lp or high altitude: step by step
- Turn off electrical power, close the manual gas shut-off valve, and let the boiler cool.
- Turn off the gas and water supply.
- Remove the four front cover screws and set the front cover aside.
- Remove the two screws below the gas valve and detach the gas inlet pipe.
- Remove the four screws at the fan motor assembly and pull the gas valve away to access the orifice.
- Remove the two screws holding the orifice, then remove the orifice and gasket.
- Install the correct orifice from the approved kit, making sure the gasket is seated.
- Reinstall the gas inlet pipe and secure all screws without overtightening.
- Set DIP switches for gas type and altitude.
- Leak test, then verify CO2 and offset as described for gas/air ratio adjustment.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 138. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.