Navien Boiler: Fill and leak test the water system
Fill and leak test the water system on a Navien boiler: Fill test to confirm the water system is installed correctly before firing the burner.
Applies to: NCB700 water system
How to fix fill and leak test the water system: step by step
- Confirm water chemistry meets the limits before filling.
- Open the pressure relief valve by lifting the lever on top, and loosen the air vent cap.
- Loosen the manual and automatic air vents and close the boiler drain valve.
- Fill the boiler to the correct system pressure. Typical cold fill for a residential system is 12 psi. Never exceed the relief valve setting.
- Close the pressure relief valve when the system is full, and make sure it is closed before testing or operating.
- At initial fill and during start-up and testing, check the whole system for leaks and repair any before continuing.
- Keep the boiler full of water before firing the burner.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 110. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.