Navien Boiler: Exhaust venting installation
Exhaust venting installation on a Navien boiler: Vent per the approved Category IV system and keep the termination clearances.
Applies to: NFB-301C/399C
How to fix exhaust venting installation: step by step
- Use only approved vent materials: PVC/CPVC Schedule 40 or 80 solid core, approved polypropylene or approved stainless steel (USA).
- In Canada, use Type BH special gas vent Class IIA (PVC), IIB (CPVC) or IIC (polypropylene/stainless steel), certified to ULC-S636.
- Do not mix components from different vent system manufacturers.
- Keep at least 12 in above the highest anticipated snow level or grade for roof or vertical terminations (18 in in Canada).
- Keep at least 12 in clearance from any obstruction for the termination.
- Keep the vent within the maximum length and elbow limits in the venting table.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NFB-C quick installation guide, p. 3. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.