Navien Boiler: Enable zone pump 4
Enable zone pump 4 on a Navien boiler: Zone pump 4 replaces the DHW recirculation pump on the boiler's connection to run a fourth heating zone. Each zone pump is rated max 2.5 A.
Applies to: NCB700 with 4-zone pump system
How to fix enable zone pump 4: step by step
- From the front panel, press Menu and select 2. Space Htg Operation > 2. Zone Settings > Zone Pump System.
- Or on the main panel, press Back and Menu together for 3 seconds, then select 3. Parameter Settings > 16. Zone4 Settings > Enable.
- Note that zone 4 pump runs on the recirculation thermostat input.
- Note that with Zone4 Settings enabled, DHW recirculation is not available even in zone valve mode. Disable this parameter if DHW recirculation is needed.
If the unit shows an error code, look it up: Navien Boiler codes
More settings shortcuts tips for boiler
Source: NCB700 Installation & Operation Manual, p. 51. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.