Updated · by Aurora Star Tech Inc.

Determine the common vent length on a Navien boiler: Total vent length is horizontal width plus vertical height. Use the total BTU/H of all units to read the allowed length from the table.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NCB700 common vent

How to fix determine the common vent length: step by step

  1. Add the BTU/H input of every unit in the cascade to get the total BTU/H.
  2. Measure the horizontal width (W) and vertical height (H) of the common vent.
  3. Add W and H to get total length (L = W + H).
  4. Compare the total length with the vent length table for the matching BTU/H load and pipe diameter.
  5. Count each 90° elbow as 8 linear ft (2.4 m) of vent length.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Navien NCB700 Installation & Operation Manual, pp. 93-94. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.