Navien Boiler: Connecting the boiler power supply
Connecting the boiler power supply on a Navien boiler: The boiler runs on a dedicated 110-120V AC supply with a breaker. It must not be connected to 220-240V. Only licensed professionals should make the connection.
Applies to: NCB700 electrical connection
How to fix connecting the boiler power supply: step by step
- Do not connect power until all water and gas piping is complete and the boiler is filled with water.
- Use a dedicated 110-120V AC circuit with a breaker. Do not connect to 220-240V.
- The factory plug is 5 ft, 3-prong and rated 12 A. It plugs into any grounded outlet next to the boiler.
- If local code requires hardwiring, disconnect power, cut the cord about 2 in below the cabinet, and remove the four front cover screws.
- Splice the black (hot), white (neutral) and green (ground) wires to the supply with field-supplied twist-on connectors. Strip about 1/2 in of sheath first.
- Make sure the boiler is properly grounded. Do not use gas or water pipes as the ground, since plastic pipe or dielectric unions may stop proper grounding.
- Use a surge protector to protect the boiler from power surges.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 80. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.