Navien Boiler: Condensate neutralizer maintenance
Condensate neutralizer maintenance on a Navien boiler: Check neutralizer media and outlet pH regularly. Test once a year with pH strips or an electronic meter. Replace the media when pH falls below the local water authority minimum, or below 6.0 if no minimum is specified.
Applies to: NCB700 condensate neutralizer
Common causes of condensate neutralizer maintenance
- Neutralizing media used up by condensate flow
- Condensate trap debris
How to fix condensate neutralizer maintenance: step by step
- Periodically check the media level in the neutralizer.
- Test the outlet pH at least once a year.
- Replace the neutralizing media when pH drops below the local minimum, or below 6.0 if none is set.
- During the first year, check the neutralizer every few months for depletion.
- Once a year, drain the condensate trap, clean out debris and refill with fresh water through the access port.
- Order replacement media from your local Navien distributor.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 27-28. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.