Navien Boiler: Condensate drain disposal and connection
Condensate drain disposal and connection on a Navien boiler: Condensate is acidic (pH 3-5). Follow local codes. Draining into a laundry tub is recommended because detergent neutralizes the acid. Options: direct to an external drain, through a neutralizer then to drain, from a higher boiler into a laundry tub, or via a condensate pump into a laundry tub. A pump is used when the drain run is long or the boiler sits lower than the tub.
Applies to: NCB700 condensate drain
How to fix condensate drain disposal and connection: step by step
- Choose a disposal option that meets local codes.
- Connect a drain line to the 1/2 in NPT fitting at the bottom of the boiler.
- Use only corrosion-resistant drain line such as PVC or CPVC.
- Do not reduce the fitting or drain line below 1/2 in.
- If using a pump, make sure it handles at least 2 GPH per boiler in the system.
- If not using a pump, pitch the drain line down at least 1/4 in per foot.
- Where the grade is insufficient, install a drainage pump rated for boiler condensate.
- Fill the condensate trap with water after installing the drain pipe.
- Do not cap or plug the condensate line and keep it from freezing.
- Never let people or animals drink condensate.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 25-26. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.