Navien Boiler: Check and adjust gas valve offset at low fire
Check and adjust gas valve offset at low fire on a Navien boiler: Check the gas valve offset at low fire against the altitude kit table. Adjust only if the reading is out of range.
Applies to: NCB700 gas valve, low fire offset
Common causes of check and adjust gas valve offset at low fire
- Offset reading is outside the range for the installed altitude kit
How to fix check and adjust gas valve offset at low fire: step by step
- Open the offset pressure port by loosening the screw two turns, or use the mechanical manometer port.
- Connect a manometer to the offset pressure port. On a dual port manometer, use the positive pressure side.
- Open several DHW fixtures on full hot.
- Set the boiler to 1-stage MIN mode (see 12.6.7 Setting the Special Operation Modes).
- Read the offset value at low fire and compare it to Table 3.
- If out of range, remove the screw-on cover over the gas valve set screw. The set screw is shown in Figure 10.
- Using a 5/32 in or 4 mm Allen wrench, turn the set screw no more than 1/4 turn. Clockwise raises the offset; counterclockwise lowers it.
- Recheck the offset at low fire.
- Do not check or adjust the offset at high fire.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NCB700 installation and operation manual, p. 144. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.