Navien Boiler: Allow the BAS to switch the boilers on and off

Updated · by Aurora Star Tech Inc.

Allow the BAS to switch the boilers on and off on a Navien boiler: To let the building automation system turn the boilers on or off while Modbus is enabled, use one of the two methods below.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NFB700-500C/600C/800C/1000C with Modbus RTU enabled

How to fix allow the bas to switch the boilers on and off: step by step

  1. Set main DIP switch 7 to ON (Space Heating Thermostat-Unused), or
  2. Short the T/S ZONE3 port.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

More settings shortcuts tips for boiler

Source: Navien Modbus RTU installation & operation manual, p. 4. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.