Navien Boiler: Air removal from the system piping

Updated · by Aurora Star Tech Inc.

Air removal from the system piping on a Navien boiler: Air vents and bleeders must be placed around the system to purge air during commissioning. An air separator or air eliminator must be fitted, usually higher in the system where there is guaranteed positive pressure, such as near the water fill and expansion tank.

Homeowner with a boiler problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NCB700 system piping

Common causes of air removal from the system piping

  • Air trapped in the system water

How to fix air removal from the system piping: step by step

  1. Place air vents and bleeders at high points across the system.
  2. Install an air separator or eliminator and follow its installation instructions.
  3. Locate the air removal device where pressure is guaranteed positive, near the water fill and expansion tank.
  4. Use straight pipe with at least 1/2 in (12 mm) inside diameter on the upstream side of all pumps.
  5. Provide an expansion tank per the guidance on p. 22.
  6. In Massachusetts, install a vacuum relief valve in the cold water line per 248 CMR. Similar rules apply in New Jersey.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Boiler codes

Source: Navien NCB700 installation and operation manual, p. 29. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.