Navien Boiler: Adjust gas/air ratio (CO2) with combustion analyzer
Adjust gas/air ratio (CO2) with combustion analyzer on a Navien boiler: Check and adjust CO2 at MIN and MAX firing using the emissions port.
Applies to: Propane gas/air ratio check
How to fix adjust gas/air ratio (co2) with combustion analyzer: step by step
- Loosen the screw, rotate the plate and remove the gasket to reach the emissions monitoring port.
- Insert the analyzer probe into the port.
- Activate multiple zones and set the boiler to 1-stage MIN mode. Measure CO2.
- Compare the reading with the CO2 table. If it is not within 0.5% of the listed value, adjust the set screw.
- Activate multiple zones and set the boiler to 2-stage MAX mode. Measure CO2 again.
- If the reading is out of range, adjust the set screw.
- To adjust, use a 5/32 in or 4 mm Allen wrench and turn the set screw no more than 1/4 turn. Clockwise raises CO2; counterclockwise lowers CO2.
- Set screw is behind the screw-on cap; remove the cap to reach it. Figure reference is 7 or 9.
If the unit shows an error code, look it up: Navien Boiler codes
Source: Navien NFC-H propane and high altitude conversion guide, p. 2. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.