Navien Air Conditioner: Replace outdoor temperature sensor (T3, T4, T5, T7)
Replace outdoor temperature sensor (T3, T4, T5, T7) on a Navien air conditioner: Sensors are replaced in the outdoor unit. Check the sensor against the user interface before replacing it, because a bad PCB can also show a wrong temperature.
Applies to: NAA17V36-24K/36K, NAA17V60-48K/60K
Common causes of replace outdoor temperature sensor (t3, t4, t5, t7)
- Sensor reads a temperature that does not match the resistance of the sensor
How to fix replace outdoor temperature sensor (t3, t4, t5, t7): step by step
- Turn off the circuit breaker for the unit.
- Remove the 10 top cover screws and the 18 bottom cover screws, then take off the upper covers and side panels.
- Pull the clip that holds the thermistor.
- Lift the thermistor out of its holder.
- Unplug the thermistor connector from the PCB and remove the sensor.
- Before replacing, compare the measured resistance with the temperature shown on the user interface. If the resistance matches but the displayed temperature is wrong, replace the PCB instead.
If the unit shows an error code, look it up: Navien Air Conditioner codes
Source: Navien NAA air conditioner service manual, p. 48. Written in our own words as a summary; always check the original manual.
General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.