Navien Air Conditioner: Replace compressor

Updated · by Aurora Star Tech Inc.

Replace compressor on a Navien air conditioner: The compressor is replaced by recovering refrigerant, cutting the pipes, fitting a new compressor, brazing, evacuating and recharging.

Homeowner with a air conditioner problem? Call (647) 657-2977 or book a service call — licensed technicians across Vaughan and the GTA.

Applies to: NAA17V36 and NAA17V60

How to fix replace compressor: step by step

  1. Turn off the circuit breaker.
  2. Remove the 10 top cover screws and the 10 screws on the top and bottom side panels, then remove the top cover and panels.
  3. Remove the compressor sound blanket.
  4. Recover all refrigerant from the refrigerant circuit before any heat work.
  5. Disconnect the faston connectors from compressor terminals U, V and W. Note their positions first.
  6. Braze off the suction and discharge pipes with a torch.
  7. Remove the 3 nuts in the rubber pad section and lift the faulty compressor out.
  8. Install the new compressor. Insert the rubber pads before tightening the fixing nut.
  9. Remove the rubber caps from the new compressor's suction and discharge pipes to release the nitrogen.
  10. Braze the suction and discharge pipes to the compressor.
  11. Connect the power cable to the compressor terminal board and fit the sound-proof covering.
  12. Evacuate the unit with a vacuum pump down to 350 microns.
  13. After vacuuming, open the service valves. If a recovery unit is used, charge refrigerant.
Safety: Gas, electrical and refrigerant work must be done by a licensed technician. Turn off power and gas before servicing, never bypass a safety control, and always follow the manufacturer's manual for your exact model.

If the unit shows an error code, look it up: Navien Air Conditioner codes

Source: Navien NAA air conditioner service manual, p. 51-52. Written in our own words as a summary; always check the original manual.

General guidance for qualified technicians. The manufacturer's installation and service manual and local codes always take priority. Aurora Star Tech is not affiliated with, endorsed by or sponsored by any equipment manufacturer; brand and model names are used only to identify equipment and belong to their owners.